PA-90D Spec Sheet: 

Spec Sheet | Drawings | Literature

You can copy and paste this information into your word processor.

Enclosure
NEMA 4X FRP (fiberglass reinforced polyester) padlockable.
16" H x 14" W x 6"D
NEMA 4 carbon steel and NEMA 4X stainless steel are optionally available. (Size will depend upon overall system requirements and customer specification).

Power Required
120 VAC / 1 PH / 60 HZ (Standard)

Circuit Breaker
Sized to pump and motor requirements. (10 amp standard).

Compressor
1.0 CFM @ 80-psig

Pressure Settings
Pump "ON" @ 80 P.S.I Pump
"OFF" @ 100 P.S.I.

Pressure Gauge
2.5" 0 – 160 psig. Internally mounted.

System Timer
0 - 10 minutes adjustable.

Bypass Relief
Adjustable to system operating requirements. (Typically set @ 110-psig)

Pressure Switch
120-vac with “auto-unloader”

Operating Modes
"REMOTE" / "LOCAL"

Manual Controls
"OPEN"
"CLOSE"
"EMERGENCY STOP" palm button

Diagnostic Lights
"Breaker ON"
"Power ON"
"Remote"
"Open"
"Close"
"E-Stop engaged"

Weight
25 Lbs. Standard.
Custom systems will vary depending upon overall system configuration.

Copyright 2010 Pratt Control Systems. All rights reserved. Pratt Control Systems is a subsidiary of Mueller Water Products, Inc.